HONEYWELL霍尼韦尔执行器M6284F1039-S 产品资料: Minimum load: 10 mA at 5 VDC Mechanical life: 1,000,000 operations Electrical life: Make: 50,000 times, Break: 30,000 times Ambient operating temperature ?20 to 60°C (with no condensation or icing) Storage temperature ?40 to 70°C (with no condensation or icing) Ambient operating humidity 25% to 85% (with no condensation) Storage humidity 25% to 85% (with no condensation) Altitude 2,000 m max. Terminal screw tightening torque 0.54 N·m Terminal wiring method Recommended wire Solid wire: 2.5 mm2 Twisted wires: AWG16, AWG18 Note: 1. Ferrules with insulating sleeves must be used with twisted wires. 2. Two wires can be twisted together. Recommended ferrules Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact Case color Munsell 5Y8/1 Case material ABS resin (self-extinguishing resin) UL94-V0 Weight Approx. 110 g Mounting Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N·m) Dimensions 22.5 (W) × 90 (H) × 100 (D) mm K8AB-PH1 4 Nomenclature Front Indicators *1.The input across L1 and L3 is used for the internal power supply. Therefore, the power indicator will not be lit if there is no input across L1 and L3. *2.Use either a solid wire of 2.5 mm2 maximum or a ferrule with insulating sleeve for the terminal connection. The length of the exposed current-carrying part inserted into the terminal must be 8 mm or less to maintain dielectric strength after connection. Recommended ferrules Phoenix Contact ? Al 1,5-8BK (for AWG16) ? Al 1-8RD (for AWG18) ? Al 0,75-8GY (for AWG18) *3.Tightening torque Recommended: 0.54 N·m