供应HONEYWELL霍尼韦尔执行器M7284A1038四川代理商 产品资料: Note: The input across L1 and L2 is used for the internal power supply. Therefore, the power indicator will not be lit if there is no input across L1 and L2. Setting Knobs Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with insulating sleeve for the terminal connection. The length of the exposed current-carrying part inserted into the terminal must be 8 mm or less to maintain dielectric strength after connection. Recommended ferrules Phoenix Contact ? Al 1,5-8BK (for AWG16) ? Al 1-8RD (for AWG18) ? Al 0,75-8GY (for AWG18) 2. Tightening torque Recommended: 0.49 N·m Maximum: 0.54 N·m Power indicator Relay status indicator Overvoltage knob (OVER) Undervoltage knob (UNDER) Operating time knob (T) Alarm indicator Terminal block (See notes 1 and 2.) Terminal block (See notes 1 and 2.) 0.1 Item Meaning Power indicator (PWR: Green) Lit when power is being supplied (see note). Relay status indicator (RY: Yellow) Lit when relay is operating (normally lit). Alarm indicator Overvoltage: Red Lit when there is an overvoltage. The indicator flashes to indicate the error status after the overvoltage has exceeded the threshold value while the operating time is being clocked. Undervoltage: